TraceTek® Location Systems
Even small leaks in the wrong places cause downtime, disruption,
and costly damage. Then the aftermath ties up resources in both clean-up
and repair. The lasting effects to a business can have disastrous consequences
with damage to property and stock, data loss and continued disruption
affecting the efficiency and profitability of your operation, by installing
the latest TraceTek technology which will allow you to detect leaks
at their source and pinpoint their location you can stop the damage
before it starts.
The TraceTek® product line includes sensing cables for a variety of
fluidswater, aqueous chemicals (acids, bases, waste water), fuels,
and even organic solvents. There is also a selection of alarm modules.
The design flexibility of the TraceTek® system allows you to select the
monitoring approach and layout you need, whether youre looking
for a simple detection system (for a small, isolated area) or for a
complex, multi branched locating system. The TraceTek® system is modular,
with interchangeable components for ease of design and installation.
Standard lengths of TraceTek® cable quickly plug together so that you
dont need special tools to install the system. The modular design
also means that you can easily add to the system in the future. Protech
Systems have over ten years experience in the Design. implementation,
installation and maintenance of TraceTek® systems within all types of
facilities with varying applications. We are able to bring to the table
full design and support for consultants, installers and end users along
with a full installation service within the UK. We welcome challenge
and will always be happy to discuss the feasibility of a TraceTek® system
for a clients particular application.
TTDM Alarm Module
|

TTDM ALarm Module
|
|
The TTDM alarm and locating modules are designed for use with all
TraceTek® sensing cables to detect and locate liquid leaks. When liquid is detected, the
TTDM unit sounds an alarm and displays the location of the leak in either feet, metres or zones
(defined at the time of installation) on its LCD display. The unit then continues to monitor and
will re-alarm if there are any major changes.
The unit directly monitors up to 1500 Metres (5000 Feet) of sensing cable and can
monitor up to 128 networked SIM’s (Sensor Interface Modules) or TTDM units. Each event is
logged along with time and date to the units non-volatile memory and can be forwarded to a
host computer via RS232/RS485, Modbus, 4-20 Milliamp transmitter or clean form C relay contacts.
Once the alarm condition is cleared, the module is reset with a single keystroke. In addition to
detecting leaks, the TTDM:
- Warns of fault conditions.
- Indicates when service is required based on built-in, system-wide diagnostic functions.
- Features an events history log that tracks leaks and other events.
- Settings can be customized to suit the user’s application. Software selections
include language (English, French, German, or Spanish) and units (feet, meters, or zones).
- No need for calibration or complicated setup procedure.
- Features a NEMA 12, IP 54 enclosure
Design Features:
- Multiple event tracking capability for up to 128 independent sensing circuits.
- Summary relay contacts, LED status lights, LCD information display at the TTDM master panel and
designated slave unit’s.
- Event history accessible from the front panel or via the serial port to identify: type of event,
location, & other parameters for all sensing circuit events or user adjustments and interventions.
- Complete remote operation & Monitoring through
Modbus communications or using operational TT-Supervisor software for windows.
|
Back to Top
TTSIM-1
|

TTSIM-1
|
|
The TTSIM-1 Sensor Interface Module monitors up to 5000 feet (1500 m) of
TraceTek® sensing cable. When liquid is detected, the TTSIM-1 unit communicates either
with a TTDM-PLUS Master Module or directly to a PLC or other host system using the standard
modbus protocol. Although massive sensor cable systems are possible with networked TTSIM-1’s,
their low cost makes it economical to build very robust systems with many small independent
sensing cable segments. No field calibration is required other than a map to show where the sensor
cable has been installed.
Design Features
- Responsive to two different communication protocols: proprietary when networked to a
TTDM-PLUS Master Module or generic modbus when networked to a PLC, building management system or
similar factory automation system. Protocol selection is automatic with no user intervention required.
- LED’s to indicate power, status, and communication progress.
- Simple twisted pair serial RS-485 communications out to 4000 feet without amplification.
Industry standard amplifying bridges and optical links available for greater distances.
- Operates on 24 Vac 50/60 Hz either from a local supply or provided in the same cable that is used for data transfer.
- Each SIM unit has a unique address assigned with software - no dip switches.
- Up to 31 SIM units when networked to a TTDM-PLUS Master Module.
- Up to 123 SIM units when connected via twisted pair to an RS-485 communication port.
- DIN rail mounted for easy installation.
- NEMA-4X enclosure available for harsh or outdoor locations.
|
Back to Top
TTSIM-1A
|

TTSIM-1A
|
|
The TTSIM-1A Sensor Interface Module monitors up to 500 feet (150 m) of TraceTek® sensing cable.
When liquid is detected, the TTSIM-1A unit indicates the leak with an LED, and switches a relay to
provide local voltage-free contact closure. The TTSIM-1A can also communicate to a host monitoring
system such as a TTDM-PLUS or directly to a PLC or other host system using the standard MODBUS protocol.
The low cost of the TTSIM-1A makes it economical to build very robust systems with many small independent
sensing cable segments. No field calibration is required.
Design Features
- Voltage-free contacts for alarm signaling.
- LED’s to indicate power, leak, cable trouble, and communication status.
- Responsive to a variety of communication protocols. Protocol selection is automatic.
- Simple twisted pair serial RS-485 communications up to 4000 feet without amplification.
- Available for 24, 120 or 220 Vac 50/60Hz power supply.
- Each SIM unit has a unique address assigned with software – no dip switches.
- DIN rail mounted for easy installation.
- Enclosures available for stand-alone indoor or harsh outdoor installations.
|
Back to Top
TT-SIM-2
|

TT-SIM-2
|
|
The TT-SIM-2 Sensor Interface Module monitors up to 150 meters (500 feet) of TraceTek® sensing cable.
When liquid is Detected, the TT-SIM-2 unit indicates the leak with an LED, displays the location of
the leak on its LCD display and switches a relay to provide local voltagefree contact closure. The
TTSIM-2 can also communicate to a host monitoring system such as a TraceTek® TTDM-128 or directly to a
PLC or other host system using standard protocols. The low cost of the TT-SIM-2 makes it economical to
build very robust systems with many small independent sensing cable segments. No field calibrationis required.
The TT-SIM-2 can be used as a stand-alone leak detection alarm unit, or in networks with other TraceTek®
TT-SIM, TT-NRM or TTDM-128 modules. The TT-SIM-2 can be configured using a Palm™ OS or Pocket PC™ handheld
PDA, a Microsoft Windows™ based PC, or a TraceTek TTDM-128 network master module.
Design Features
- Voltage-free contacts for alarm signaling
- LED’s to indicate power, leak, cable trouble, and communication status.
- Leak location display on LCD.
- Responsive to a variety of communication protocols. Protocol selection is automatic.
- Simple twisted pair serial RS-485 communications up to 1200 meters (4000 feet) without amplifi cation.
- Available for 24, 120 or 230 Vac 50/60 Hz power supply.
- Each TTSIM-2 unit has a unique address assigned with software – no switches.
- Relay software selectable for normally energized or normally deenergized operation
- DIN rail mounted for easy installation.
- Enclosures available for stand-alone indoor or harsh outdoor installations.
|
Back to Top
TTA-SIM Alarm Module
|

TTA-SIM Alarm Module
|
|
The TTA-SIM has been designed to give a local alarm whilst communicating precise
details to a monitoring network. The unit can be used with the full range of TraceTek
cables and sensors along with Aquentis probes. Up to 150 Metres (500ft) of sensing cable as
well as 500 Metres (1,666 ft) of non-sensing Jumper cable can be connected to each unit.
When liquid is detected the unit alarms and indicates the leak by a red LED and audible
alarm whilst switching a form C relay contact. The leaks location is calculated and can be
communicated to the host system via the network (if connected). With the TT-SIM-2 option the
leaks location is also displayed on the built in LCD display.
The TTA-SIM can be used as a stand alone unit or can be installed in networks with other
TTA-SIM, TT-SIM, TT-NRM or TTDM-128 modules.The unit can be configured using a Microsoft Windows™
based PC or a TraceTek® TTDM-128 network master module.
Design Features
- Rugged polycarbonate enclosure for tough environments.
- 60dB audible alarm with mute function
- Volt free clean change over contacts for alarm rated at 2 Amps 250 Vac or 30Vdc
- LED indication of: Leak, Cable Break and communication status.
- Optional LCD display for Leak location display.
- Simple shielded pair RS-485 communications using a variety of communications protocols
(Modbus™ OptoMux™ or Johnson Controls Metasys™)
- Versions available for 120 or 230Vac 50/60 Hz power supplies
|
Back to Top
TT-NRM
|

TT-NRM
|
|
Description
The TraceTek® TT-NRM Network Relay Module provides the capability to add up to 320
individual alarm relays to a TraceTek TTDM-128 / TTSIM leak detection network. The TT-NRM
communicates with the TTDM-PLUS/128 via the same RS-485 network used for TTSIMs. The TT-NRM
can be installed in a wide variety of configurations, allowing many leak detection system layout possibilities.
Expandable
The TT-NRM is supplied as a base unit (with power supply, communications interface, DIN rail
and end blocks) and separate relay modules. Each relay module contains 2 independently addressable
relays. Up to 16 relay modules can be installed on each base unit, and up to 10 base units can be
connected to a single TTDM-PLUS. The leak detection network can be expanded at any time with minimal effort.
Versatile
The TT-NRM can be installed in large panels, or wall mounted in its own optional enclosure. TT-NRMs can
be centrally located with the TTDM-PLUS, or distributed throughout the leak detection network to minimize
wiring costs. The TT-NRM can be used to operate valves, control audible or visual alarms, or interface with other
control systems.
|
Back to Top
Sensing Cables
|

TT1000
|
|
TT1000 Sensing Cable
TT1000 sensing cable detects the presence of water at any point
along its length. Small but rugged, TT1000 cable is extremely
resistant to abrasion and corrosion, and has a smooth design that
dries quickly. It is designed for a range of applications in commercial
buildings, including:
- Computer room subfloors
- Telecommunication rooms
- HVAC equipment
- Pipes and drip pans
- Storage areas
|
TT1000 Connectors
|
|
TT1000 sensing cable comes with factory installed plastic connectors.
Standard lengths of cable plug together quickly, and require no
special tools to install. |
|

TT3000
|
|
TT3000 Sensing Cable
TT3000 sensing cable detects the presence of conductive liquids
(most acids and bases and even deionized water) at any point along
its length. Raychems conductive polymer technology combines
with fluoropolymer construction to make TT3000 sensing cable mechanically
strong and chemically resistant, and suitable for a range of industrial
applications, including:
- Subfloors
- Trenches
- Storage tanks
- Double containment piping
|
TT3000 Connectors
|
|
TT3000 sensing cable is available in standard lengths with factory
installed, low-profile metal connectors. Heat-shrinkable tubing
is provided to cover and protect the connectors after installation.
TT3000 is also available on bulk reels for installation in double
containment piping. Connector kits are available for installation
at access points. |
TT5000
|
|
TT5000 Sensing Cable
TT5000 sensing cable detects the presence of liquid hydrocarbon
fuels at any point along its length, but does not react to the
presence of water.
TraceTek's radiation-crosslinking and conductive-polymer technologies
combine with a rugged construction to make the cable mechanically
strong and chemically resistant. TT5000 sensing cable is designed
for a number of applications, including:
- Double contained pipes
- Underground fuel lines
- Trenches
- Tanks
TT5000 sensing cable is available in standard lengths with factory
installed, low-profile metal connectors. Heat-shrinkable tubing
is provided to cover and protect the connectors after installation.
TT5000 sensing cable is also available on bulk reels for installation
in double containment piping. Connector kits are available for
installation at access points.
|
TT5001
|
|
TT5001 Sensing Cable
TT5001 sensing cable detects the presence of liquid organic solvents
at any point along its length, but does not react to the presence
of water.
TraceTeks radiation-crosslinking and conductive polymer
technologies are used to make TraceTek TT5001 sensing cable mechanically
strong and chemically resistant. The cable is designed for a range
of applications, including:
- Subfloors
- Trenches
- Tanks
- Piping
TT5001 sensing cable is available in standard lengths with factory
installed, low-profile metal connectors. Heat-shrinkable tubing
is provided to cover and protect the connectors after installation.
|
Back to Top
Aquentis Probe
Aquentis Probe
|
|
Aquentis WDP Water Detection Probe
The WDP Water Detection probe with its unique design facilitates
either horizontal or vertical mounting from just one unit. Its low
profile means that it has a high level of stability and can be sited
below sensitive equipment, valves and pipe joints. The unit's high-visibility
yellow colour makes it easily recognisable in low light conditions,
and the heavy duty aluminium guard plate provides physical protection
where the unit is installed within harsh environments.
The probe's height can be adjusted within the housing, to accommodate
installation in conductive drip trays or to eliminate alarms caused
by acceptable small amounts of water.
|
Back to Top
AT600A
|

AT600A
|
|
The immersion sensor has been designed for use with the TraceTek® and AquiTron™ leak detection systems and is fully compatible with all TT1000 system components.
The probe has been designed for seamless integration into TraceTek® and AquiTron™ water detection
systems, either with or without sensor cable, to provide a truly versatile sensor system. For distributed
applications, up to 100 probes may be interconnected by a single jumper cable (daisy chain) and monitored for
leak location utilising either a TTDM-PLUS or TTSIM-1/1A alarm and locating modules providing leak location in
either metres, feet or zones.
Application
Applications for the immersion sensor include: overflow pipes for boilers, heating systems, unvented hot
water cylinders, blow down pipes, drainage, tank level control and applications using double containment pipe systems.
|
Back to Top
|
|